KTC Pressurized Explosion-protected Meter and Distribution Panel,Cabinet, Box(IIB、IIC)
适用范围 Application
1、爆炸性气体环境:1区、2区
2、场所中危险气体或蒸气:IIA、IIB、IIC
3、温度组别:T1~T4
4、环境温度:-20℃~+40℃
5、户内、户外

1、Explosive gas atmospheres:Zone 1&2
2、Dangerous gases or vapors zone: IIA、IIB、IIC
3、Temperature classes:T1~T4
4、Environment temperature:-20℃~+40℃
5、Indoor and outdoor

KTC正压防爆仪表、配电盘、柜、箱(IIB、IIC)定做

KTC正压防爆仪表、配电盘、柜、箱(IIB、IIC)定做 主要技术参数
1、防爆标志:Expdem II BT4 Expdem II CT6 2、防护等级IP54(可达IP56)
3、副(柜箱)内供电220VAC±10% , 50-60HZ, 10A
4、输入气源:0.4-0.8MPa,净化空气或氮气等保护气体
5、进气口为:G1/2 6、换气量为:10-20m3/h
7、换气时间:10-30min(由防爆检测单位确定,tp=5×V/Q, tp:换气时间,V:主腔内净容量,Q:保护气体的流量)
8、耗气量为:2-8m3/h (根据盘、柜的容积和面板操作元件的多少及其密封程度而定)
9、功能指标:
a)仪表、电器供电前,对盘、柜内剩余空气按启动按钮自动换气。换气结束自动维持正压值250Pa±100Pa,此时可向盘、柜内仪表、电器供电
b)盘、柜内工作正压值为250Pa±100Pa
c)内部正压值<150Pa时,自动补气
d)内部正压值<80Pa时,自动声光报警
e)内部正压值<50Pa时,自动切断电源(2区危险场所使用时,需此功能请注明)
Specification
1.Ex-marking:Expdem II BT4 Expdem II CT6 2.Degree of protection:IP54(to IP56)
3.Power supply in auxiliary panel (cabinet or box):220V±10%, 50-60HZ 10A
4. Input air source:0.4-0.8MPa,etc.protective gas such as purged air or nitrogen
5.Air input size:G1/2 6.Air purging capacity:10-20m3/h
7.Air purging time:10-30 min(determined by test station,Tp=5×V/Q, Tp:air purging time V:net volume of main compartment Q:capacity of protective gas)
8.Consumed gas:2-8m3/h(determined by volume of panel or cabinet,number of operating parts, and sealing condition)
9.Function indexes:
a)Before meter or apparatus are energized,operate the push button to purge,at the end of air puring,maintain overpressure of 250±100Pa,then automatically supply power to meter or apparatas in panel or cabinet.
b)Overpressure value in the board (Cabinet)250± 100Pa
c)Overpressure value in the board(Cabinet)<150Pa,automatically supply air
d)Overpressure value in the board(Cabinet)<80Pa,automatic alarming with sound and light
e)Overpressure value in the board (Cabinet)<50Pa,automatically disconnect power (Please refer when it used for zone 2)